AC Power Meter GPM-8212 USER MANUAL GW INSTEK PART NO. 82PM-82120MB ISO-9001 CERTIFIED MANUFACTURER This manual contains
POWER METER USER MANUAL 154-2.Wiring z Without PT or CT: z With CT SOURCE LOAD WARNING: Mak
POWER METER USER MANUAL 17 z PT Ratio setting 1) Press the button of [VPT] to appear the letters of PT on the window 2, window 3 indicates the pr
POWER METER USER MANUAL 19z Communication command COMMAND DESCRIPTION EXAMPLE F00 Data hold enable F01 Data hold disable F02 Set in maximum
POWER METER USER MANUAL 217. MAINTENANCE The following instructions are used by qualified person only to avoid electrical shock, do not perform
POWER METER USER MANUAL 23 2).Pull apart the handle from the Power Meter. Please turn the handle left and right side slightly, that will make it ea
. POWER METER USER MANUAL 2 TABLE OF CONTENTS PAGE 1. SAFETY SUMMARY…………………………………………….. 1 2. INTRODUCTION……………
POWER METER USER MANUAL 11.SAFETY TERMS AND SYMBOLS Please take a moment to review these safety terms and symbols which may appear in this manual
POWER METER USER MANUAL 3FOR UNITED KINGDOM ONLY NOTE: This lead/appliance must only be wired by competent persons WARNING: THIS APPLIANCE MUST BE
POWER METER USER MANUAL 52. INTRODUCTION GPM-8212 Power Meter is a 16-bit CPU microprocessor equipped with multifunction of full-digitized measure
POWER METER USER MANUAL 7 POWER FACTOR Range 0.001 to 1.000 Computation W ÷ (V × A) = Power factor (PF) FREQUENCY Measurement Range 40.0Hz to 4
POWER METER USER MANUAL 94-1.Function Description (1) Remote Control Indicator Remote Control Indicator (3) Status Indicator When the instrumen
POWER METER USER MANUAL 11 Display Window 【3】Kiloampere indicator. Display Window 【 2 】 Auto-range indicator. The indicator is on when the win
POWER METER USER MANUAL 13 2 Number key. Set the voltage range downward, press and hold the button for 2 seconds to enter autorange of voltage.